User Solutions
(Issue 2, 2004)
Ever
wonder how AutomationDirect
customers are applying their products?
--Check
out some of the application stories we've collected and you'll
see that AutomationDirect products are used in a
wide variety of applications across many different industries.
---
Jump
to Application Spotlight
D2-250 PLC PID loops control pumps in
residential water system
by
Peter Carman,
Wyoming Controls
___________________________________________________________________________
We used PID loops in the D2-250 CPU to control three pumps
and maintain pressure in a residential water system. The flow
demand varies from zero to 250 gallons per minute. The pumps
all have
variable speed drives with the speed reference and run commands
coming from the 250 CPU. At low flow, one pump runs alone,
as needed, to maintain the pressure. As the flow increases,
the other pumps are brought on, either in tandem with the first,
or at a constant flow rate. The flow from each pump has an
upper limit; if the total flow demand exceeds the combined
upper limits, the pressure will fall. The result is that each
pump can operate in an optimum range on its pump curve, and
a widely varying flow can be delivered and the pressure is
maintained very closely. The operator interface is a color
touch screen
that displays the pump status, flow rates, and system pressure.
All the setpoints for pump on/off and associated time delays
are easily accessible to the system operator.
D2-250
CPU maintains water pressure for city water system
by John Neiswanger,
Industrial Electronics
___________________________________________________________________________
We created a water pressure controller for a local city
water system. We used a pressure transducer to feed a water pressure signal into
the DL205 PLC system analog card. The output from an analog card is used to vary
the speed of a 75 HP well pump, controlled by a variable frequency drive, to
keep the city water system at a more constant pressure. Setpoints are entered
with a touch panel and the pressure is displayed as well. The system controls
the startup sequence, releasing the well flow to a drain and slowly cutting into
the system to prevent a pressure spike on startup. It also controls the shutdown
to prevent a pressure dip. System pressure is maintained with a PID loop in the
D2-250 processor.
DL06
PLC and EZTouch panel help move cement at bulk
handling facility
by Jeff Bailey,
Ozinga Bros. Inc
___________________________________________________________________________
We recently installed a bulk
cement handling facility. The facility offloads
cement from river barges and pneumatically conveys
the powder into a massive storage dome and truck
loading facility. The concrete dome, which can
hold 30 barge loads of cement powder, was erected
using an inflatable air form system. A MODBUS network
of four DL06 PLCs, controlled by an EZTouch Operator
Interface, outloads the cement from the dome. A
4-20 ma PID loop implemented in one of the DL06
processors controls the speed of two hydraulically
driven sweep augers. An analog radar sensor monitors
the cement level in the truck-loading silo. All
three primary functions are graphically animated
and displayed on the EZTouch panel. The "supervisory
master" DL06 controls the pneumatic conveying
system and acts as the communications hub for the
slave processors. Each processor runs local functions
independent of the master. One feature that is
particularly useful is the alarm history on the
EZTouch panel. Future planned expansions of this
facility will be simply and easily added to our
system network.
Aluminum
anodizing system controlled
with help from D2-260
PLC system and
EZText panel
by C R Williams,
Robo Systems
___________________________________________________________________________
Our system controls aluminum
anodizing. The operator uses an EZText panel to
enter the size of the job and the desired thickness
of anodizing. The D2-260 translates this into the
necessary current, voltage, and time profile required
to produce the
desired result, and controls a 300kW SCR switched
power supply that delivers the anodizing current
to the workpiece. Since the optimum waveform has
both short term (~1sec) and long term (~5min) components,
and needs precise control over two orders of magnitude
(10A to 1000A), the floating point math capabilities
of the D2-260 are used quite heavily. The environment
is extremely noisy electrically (because of the
300kW SCR phase angle switching), so the design
of the grounding and shielding, as well as software
filtering, were very important to the success of
the project.
In addition to the standard PLC on/off inputs and outputs,
analog inputs and analog outputs are used as part of the monitoring
and control process.
Cost-effective
I/O simplifies hydroelectric
plant controls upgrade
by
Lynn Mitchell,
Operations Superintendent
Lockhart Power Company
by
Andy
Feimser,
President
North Fork Electric
___________________________________________________________________________
Lockhart Power Company owns and operates a hydroelectric plant
located on the Broad River in upstate South Carolina, and services
over 6,000 direct customers and 6,000 indirect customers over
its 90-mile transmission network. The plant includes an 8-gate
dam feeding a canal that channels the water flow to the powerhouse,
which contains five turbine generators with a combined power
capacity of over 17 MW. The dam and turbine control system
receives data from power, flow, and level sensing devices to
perform monitoring and control of the dam, generators, and
associated equipment.
The previous control system, installed in 1987, was a proprietary microprocessor-based
system that had become obsolete. Lockhart required a control system that would
provide open networking capabilities, and result in a lower total cost of ownership.
The new system needed to coexist with an upgraded design of the existing hardwired
generator controls, and perform distributed, independent control at the dam and
each of the five turbine stations. Each I/O control node would replace the old
equipment in the existing control cabinets and be networked to the central control
room.
Systems integrator and vendor selection
Lockhart Power contracted North Fork Electric, a provider of hydroelectric products
and systems integration services in Crumpler, NC, to lend their expertise to
the renovation. North Fork Electric proposed a 3-tier solution. Level 1 included
new hardwired controls for manual operation of the system. Level 2 included PLC-based
control of the dam and generators in an automatic mode. Level 3 provided PC-based
redundant control and monitoring from a central location, and also supplied connectivity
to the plantwide Ethernet network.
System components
The system consists of seven DL205 micro-modular PLCs using D2-250 CPUs with
built-in PID functionality. Each of the five systems for generator control includes
analog I/O and an Ethernet communications module. The remaining two PLCs are
configured in a master/slave arrangement and control the dam gates, located upriver
from the powerhouse, via radio modems.
To reduce maintenance costs, North Fork Electric selected DL205 I/O components
to maximize commonality among all systems. The identical analog output modules
used on the generators, configured for ±10 VDC, can be configured for
the 0-5 VDC dam gate control signals by simply moving the module's range selection
jumpers. AC/DC relay modules are also used for both generator and dam control.
Two operator interfaces and a Windows NT-based PC running the LookoutDirect SCADA/HMI
software package complete the system.
System operation
In the automatic mode, the PLC can start, stop, and operate the generator via
two PID loops that control startup and synchronization of the turbine. Changing
the generator gate position varies the flow of water to the turbine, and thus
the generator's speed/frequency. To bring a generator online, it must first be
synchronized with the line frequency of the power utility. The first PID loop
slowly increases the generator speed until it reaches 90% of the setpoint, at
which point the logic switches to frequency control. Once online, the generator's
power output is varied by changing gate position.
To complete Level 2 control, North Fork Electric then installed the dam control
system. This system controls the eight canal gates located at the dam, which
regulate the flow of water downstream to the turbines. The operator enters the
required gate-position setpoints using a color touch panel connected to the dam
control's master PLC in the control room. Data is transmitted to the slave PLC,
located at the dam, via 900 MHz radio modems. The slave PLC monitors individual
gate positions using proximity switches that count teeth on the drives' gears,
and moves the gates up or down until they reach the desired positions.
North Fork Electric engineers then implemented the third and final tier of control
and monitoring. The LookoutDirect SCADA system communicates to all the PLCs over
an Ethernet network, performs supervisory control, and collects data that is
easily passed to the plant's information system.
The installation was completed in four weeks to provide Lockhart Power with a
powerful, yet simple, redundant control system that uses their familiar hardwired
design as the manual control mode.
__________________________________________________________________
Links to the current issue of Automation Notebook are found below.
Click the Back Issues link to visit the archives.